A sɛbɛnbaga: Site Editor Publish Waati: 2024-10-17 A bɔyɔrɔ: Yɔrɔ
Telefɔni yɔrɔ fanga bɛ jate telefɔni rezow joli ye, k’a sɔrɔ batiri bɛ jate a joli marayɔrɔ ye, ka rezow baaracogo ɲuman lakana. Nka, batiri ladonni kɛra gɛlɛya ye tuma bɛɛ. Ni fɛn dilannikɛlaw bɛ to ka sɔngɔw jigin sanni kɛlen kɔfɛ, batiriw cogoya dɔgɔyara kosɛbɛ. San o san, telefɔni kuran sitɛmu dɛsɛli ka ca ni 70% ye, o bɛ bɔ batiri koɲɛw la, o bɛ kɛ sababu ye ka batiri ladonni kɛ kunkolodimi ye ladonni baarakɛlaw bolo. Nin barokun in bɛ batiri tiɲɛni sababu jɔnjɔnw sɛgɛsɛgɛli jira, o min bɛ se ka kɛ kunnafoni nafama ye mɔgɔ wɛrɛw fɛ.
1. Seko ni dɔnko minɛnw lajɛlen yɔrɔ la .
O yɔrɔ la fanga-minɛnw bɛ Kɛ 40KVA UPS unit fla ye minnu bɛ Bɔ diɲɛ tɔnba dɔnnen dɔ la. Batiriw bilala sen kan san 2016. Kunnafoni caman bɛ sɔrɔ jukɔrɔ:
UPS kunnafoniw . | Batiri kunnafoni . |
Marka & Model: Duniya Mara UL33. | Marque & Modèle: 12V 100AH |
Labɛnni: 40 kVA, 2 unit bɛ sɔrɔ sigida paralɛli la, u kelen-kelen bɛɛ doni bɛ se kW 5 ɲɔgɔn ma . | Batiriw hakɛ : selilu 30 kulu kelen na, kulu 2, u bɛɛ lajɛlen ye seli 60 ye . |
Baara daminɛ don: 2006 (san 10 baara) | Baara daminɛ don: 2016 (san 5 baara) |
Zuwɛnkalo tile 6, UPS dilannikɛla ye ladonni kɛcogo kɔrɔ kɛ, ka AC ni DC kondensatɛriw bila u nɔ na (san 5 baara) ani fanw. Batiri bɔli sɛgɛsɛgɛli senfɛ (miniti 20), a sɔrɔla ko batiri bɔli baara kɛcogo ma ɲɛ. O bɔli kuran tun ye 16A ye, wa a bɔlen kɔfɛ miniti 10 kɔnɔ, seli caman ka wulicogo jigira ka se 11,6V ma, nka batiriw ka wulili ma kɔlɔsi.
A Sɔrɔla ko UPS batiri kulu fla bɛɛ ye 'koba Sɔrɔ sɛgɛsɛgɛli in senfɛ. U bɛ baara kɛ ni multimeter ye, u ye batiri chargeur ripple voltage (sumalan ni AC setting ye), o tun bɛ se 7V ma (a ka jan ka tɛmɛ maintenance standard kan). O de kosɔn, u tun bɛ sigasiga a daminɛ na ko DC filɛri kondensatɛri minnu bɛ UPS dilanbaga ka ɛntɛrinɛti injiniyɛriw nɔ na, olu ye fili kɛ, o kɛra sababu ye ka ripple voltage damatɛmɛ UPS ka DC bisi kan, o bɛ na ni batiri bonya ye.
2. dɛsɛko cogoya yɔrɔ la .
Zuluyekalo tile 22, ɲininikɛla ka jɛkulu ye lakana sɛgɛsɛgɛli kɛ tɔnbolofara dɔ la. U y’a ye ko UPS sigida minnu bɛ boon sanfɛla 5nan na, olu ka batiriw bɛ ka bonya kosɛbɛ. Ni kuran tiɲɛna ka bɔ grid la, siran tun bɛ yen ko batiriw bɛ se ka bɔ ka ɲɛ, o bɛ se ka kɛ sababu ye ka kasaara sɔrɔ. O de kosɔn, u y’a jira o yɔrɔnin bɛɛ la ko tɔnbolofara ka ladonni baarakɛlaw bɛ se ka taa a dilabaga ka ɛntɛrinɛti injiniyɛriw fɛ walasa u ka jɛ ka sɛgɛsɛgɛli kɛ yɔrɔ la ani ka gɛlɛyaw ɲɛnabɔ ni mɔgɔ saba bɛɛ ye o dugujɛ.
Batiri 12V bulging .
Zuluyekalo tile 23 wulada fɛ, o parti saba sera o yɔrɔ la. Sɛgɛsɛgɛli senfɛ, UPS unit fila bɛɛ sɔrɔla ka baara kɛ cogo bɛnnen na, ni 404V bɛ se ka wuli ka bɔ ɲɔgɔn na batiriw kama (ka kɛɲɛ ni set paramètres ye). A dilannikɛla ka ɛntɛrinɛti injiniyɛriw ye fluke 287C multimeter (hakɛ caman) kɛ ka batiri chargeur ripple voltage suman, o tun bɛ 0,439V ɲɔgɔn bɔ. A fluke 376 clamp meter (a ka tiɲɛni duguma) suman 0,4V lamini na. Minɛn fila ninnu ka jaabiw tun bɛ ɲɔgɔn na ani u binna Ripple voltage typique kɔnɔ minɛnw na (a ka c’a la, u ka dɔgɔ ni 1% ye bisiw ka voltage la). O y’a jira ko DC kondensatɛri minnu bɛ u nɔ na, olu bɛ sariyaw labato ani ka baara kɛ cogo bɛnnen na. O la, hakilina min tun bɛ siga la ka tɛmɛ, o ye ko kondansɛri caman cili ye ripple voltage (kurunba) caya kojugu ani batiri bonya ma ban.
Multimeter: 0,439V .
Clamp Meter: A bɛ se ka kɛ 0,4V ye .
UPS sitɛmu tariku sɛbɛnw seginnkanni y’a jira ko, zuwɛnkalo tile 6, UPS yɔrɔ fila bɛɛ tun ye batiri bɔli sɛgɛsɛgɛli kɛ miniti 15 kɔnɔ. Seko ni dɔnko sɛgɛsɛgɛli kɛlen kɔfɛ, 6 min bɛ kɛ ka ɲɔgɔn ta, o kɛra, o kɔfɛ, a dilannikɛla ka ɛntɛrinɛti injiniyɛriw ye batiri bɔli sɛgɛsɛgɛli kɛ miniti 14 kɔnɔ. Kɔrɔbɔli kɔfɛ, UPS sitɛmu ye a yɛrɛma, a bɛ sanga 12 ɲɔgɔnna sara naani tugu ɲɔgɔn na, n’a dakun kelen-kelen bɛɛ farala ɲɔgɔn kan ni miniti 1 ye, n’a kuncɛra 5:32 waati la zuwɛnkalo tile 9. Kabini o waati, batiriw tora chargement mode la.
UPS batiriw labɛncogo fɔlɔ sɛgɛsɛgɛli wɛrɛw ye ninnu jira:
Batiri ɲɛnamaya tun bɛ kalo 48 (san 4) kɔnɔ, hali ni batiri 12V ɲɛnamaya yɛrɛ ka kan ka kɛ san 5 ye.
Chargement equaliqué tun sigilen bɛ 'enabled.' .
Sara sisan dan tun sigilen bɛ 10A kan.
A daminɛ ka wuli ka taa zariji bɛnkan na, o bilala 1A la (sistɛm tun bɛna wuli a yɛrɛma ka kɛ chargement equalised ye ni float charge current tɛmɛna 1a kan, hali ni default value for this model is 0.03c10~0.05c10, o kɔrɔ ye ko bɛnkan bɛ daminɛ ni float charge current sera 3-5a. Nka, a ma se ka kɛ ko a bɛ se ka kɛ 0. tun bɛna daminɛ ni float charge current sera 1A ma).
Chargement lakanani waati bɛnkan tun bɛ kɛ miniti 720 kɔnɔ (sarali kelen min bɛ bɛn ɲɔgɔn ma, o tun bɛna jɔ a yɛrɛma sanga 12 kɔfɛ).
3. Sɛgɛsɛgɛli kɛra dɛsɛ sababuw kan .
Ka da nin ko kɛlenw kan, dɛsɛ taabolo bɛ se ka sɛgɛsɛgɛ nin cogo la:
Nin UPS sitɛmu batiri kulu fila tun bɛ baara la kabini san 4 (12V batiriw ka baarakɛ waati ye san 5 ye), wa batiri seko tun dɔgɔyara kosɛbɛ. Nka, sani a ka dɛsɛ, batiri kɛnɛma cogoya tun bɛ cogo la, a bonya taamasiɲɛ si tun tɛ a la. UPS tariku sɛbɛnw lajɛ wɛrɛ k’a ta san 2019 zanwuyekalo tile 30 (sɛbɛn minnu bɛ kɔn nin don ɲɛ, olu bɔra kɛnɛ kan) ka se zuwɛnkalo tile 6 san 2020 ma, o y’a jira ko UPS ka sigikafɔ kɛra 12 bɛnkan ye, n’a kuntaala jan tɛ tɛmɛ miniti 15 kan. O b’a jira ko zarizi kuntaala kelen min sigilen bɛ UPS sitɛmu kɔnɔ sani a ka ladonni kɛ, o tun ka surun kosɛbɛ, miniti 15 dɔrɔn, wa UPS sitɛmu ka chargement waati kunkurunnin kɔnɔ, o tɛna kɛ sababu ye ka batiriw wuli.
Ladonni ni kondansɛri caman cili kɔfɛ, UPS sitɛmu daminɛna kokura. Contrôle logique (kunnafoni-falen-falen) hakilina ye batiri in jira ko a ni a cɛsirilen don kokura, o de la a ye miniti 6 ɲɔgɔnna chargement (sarali) daminɛ ka sɔrɔ ka wuli ka taa charge (sara) la. Nka, miniti 14 bɔli sɛgɛsɛgɛli kɔfɛ, UPS sitɛmu y’a daminɛ ka chargement equaliqué daminɛ walasa ka batiriw falen pewu. Batiri minnu bɛ baara la san 4 kɔnɔ, u ka kɔnɔna charge marali seko tun tiɲɛna, o kɛra sababu ye ka flot charge current tɛmɛ 1A kan, o ye 1A equalisized charge threshold daminɛ UPS system kɔnɔ (o modeli in nafa dafalen ye 3~5a float charge current ye ka charge equaliqué, nka kun dɔw la, maintenance baarakɛlaw ye nin fɛn caman sɛmɛntiya ka kɛ 1a ye). O kɛra sababu ye UPS sitɛmu ka segin-ka-bɔ chargement (sarali) daminɛ siɲɛ caman fo ka se batiri kɔnɔna da wulilen ka ciriw laban ma (n’o tɛ, UPS sitɛmu tun bɛna t’a fɛ ka segin ka chargement kɛ ɲɔgɔn kan, o min tun bɛ se ka kɛ sababu ye ka batiri kulu ka tasuma minɛ). O waati kɔnɔ, batiriw ye chargement cyclage 48 kɛ ɲɔgɔn fɛ sanga 48 kɔnɔ (sɛrɛkili kelen-kelen bɛɛ bɛ jɔ miniti 1 dɔrɔn sanga 12 o sanga 12 sani u ka chargement equaliqué daminɛ kokura). O ɲɔgɔnna chargement (sarali) janyalen kɔfɛ, batiriw labanna ka bonya, wa hali ventilateurs (fiɲɛbɔlanw) bɛ tiɲɛ.
4. Kuncɛli
Ka da kɔlɔsiliw ni sɛgɛsɛgɛli kan minnu fɔra sanfɛ, batiri tiɲɛni sababu minnu bɛ nin UPS sitɛmu kɔnɔ, olu ye ninnu ye :
O sababu tilennen tun ye UPS sitɛmu ka chargement paramètres sigicogo jugu ye, o min kɛra sababu ye ka chargement equalisé continue kɛ sanga 48 kɔnɔ ni miniti 1 dɔrɔn ye ɲɔgɔndan kelen-kelen bɛɛ ni ɲɔgɔn cɛ. Hali batiri kura tɛna o ɲɔgɔnna chargement (sarali) janyalen ni fangama in muɲu, o bɛ na ni batiri bonya dɛsɛ ye nin ko in na.
UPS sitɛmu modɛli ye dilan fɔlɔ ye ni baarakɛcogo dan ye. Nin UPS modɛli kɔrɔ in (min dabɔra a san 20 ye nin ye) tun tɛ ni ' zarida kelen-kelen bɛɛ lakanani waati ye' sigicogo (mara suguya wɛrɛw bɛ nin cɛmancɛ in sigi cogoya la tile 7), o bɛ na ni zarizi sɛgɛsɛgɛli caman kɛli ye min bɛ taa ɲɛ.
Batiriw ka baara kɛcogo tun tiɲɛna ka da a si hakɛ kan (san 4 baara la), ni a bɔli seko dɔgɔyara ani a ka charge marali man ɲi. Sani zuwɛnkalo tile 6 ka se, bɛnkan min bɛ kɛ ka taa ni a ye, o bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye min bɛ se ka kɛ fɛn ye. UPS sitɛmu nafa ye 3~5A ye, o bɛɛ n’a ta, ladonni baarakɛlaw y’a sɛmɛntiya cogo min tɛ se ka ɲɛfɔ ka kɛ 1A ye.
UPS ka sigida tun bɛ baara la kabini san 14, a si tɛmɛna a san hakɛ kan kosɛbɛ, o kɛra sababu ye ka sumani filiw kɛ fɛn ye min tɛ se ka bali. O filiw bɛ se ka kɛ sababu ye ka sistɛmu in daminɛ siɲɛ caman ka chargement equaliqué daminɛ k’a sababu kɛ current detection tiɲɛnen ye.
A nisondiyalen don ko ciriw da wulilen min bɛ batiriw kɔnɔ, o ye UPS sitɛmu bali ka t’a fɛ ka chargement cycles (sarali) segin-ka-bɔ ɲɔgɔn na, chargeur (sarali) naaninan kɔfɛ, o cogo la, a bɛ se ka kɛ sababu ye ka batiriw ka tasuma minɛ.
5. Labɛnni fɛɛrɛ minnu bɛ kɛ ka ɲɛsin dɛsɛ ma .
Labɛnni fɛɛrɛw bɛ sɔrɔ a fan fila de la:
A fɔlɔ, UPS batiri chargement paramètres caman sɛmɛntiya waati dɔ kɔnɔ:
Aw bɛ zarizi sigicogo bɛnkan bali UPS sitɛmu kɔnɔ.
Aw bɛ trigger current ladilan ka bɔ chargement flotte la ka taa chargement equalisé la ka taa 3a la (hali ni 3a bɛ dɔgɔya dɔɔnin hali bi, bawo a daminɛ hakɛ ye 3A ye, nka a tun sigilen bɛ 1a kan fɔlɔ).
Aw bɛ chargement protection equalisé waati ladilan ka se lɛri 1 ma (a tun bɛ kɛ ka tɛmɛ lɛri 12 kan).
Filanan, tɔnbolofara biro ye batiri kulu fila bila u nɔ na ni batiriw ye minnu bɛ kɛ kɔfɛ, nka batiriw bɛ se ka kɛ 50 Ah dɔrɔn ye, o la, u bɛ se ka kɛ waati dɔɔnin dɔrɔn kɔrɔtɔko ye. Laɲiniw bɛ ka kɛ walasa ka doni in bɔ UPS siratigɛ la ka taa fanga sɔrɔyɔrɔ wɛrɛw la don nataw la, walasa ka kuran lakanani koɲɛw ɲɛnabɔ kosɛbɛ.
Baarakɛla bɛ musaka caman kɛ san o san UPS sitɛmu ladonni baara la, o bɛɛ n’a ta, k’a sababu kɛ ladonni baarakɛlaw ka dɛsɛ n’u ka jateminɛbaliya ye, u yɛrɛ ye fili kɛ ka UPS sigida nafaw sɛmɛntiya, o min tɛ se ka da a la tiɲɛ na. A bɛ fɔ ko UPS dilannikɛla ka u ka fɛn dilannenw ladon kosɛbɛ, wa u kana o fili jɔnjɔnw kɛ don nataw la, k’u ka ladonni baara kɛcogo ɲɛ. O waati kelen na, a jirala ko baarakɛla fana b’a janto kosɛbɛ ladonni baara nataw la minnu bɛ kɛ UPS dilannikɛla fɛ ani ka jateminɛ kɛcogo dɔ sigi senkan walasa ka to ka UPS sigida baarakɛcogo lakanalen ni dannamɔgɔya yiriwa.
Batiri kɔlɔsili sira (BMS) ni Sow ɲɛnabɔli sira (BMS): Mun na u fila bɛɛ nafa ka bon?
Dfun Tech: Ka Batiri baara ni a ɲɛnabɔli waati hakilitigi ɲɛminɛ .
Batiri kɔlɔsili fɛɛrɛw jɛnsɛnnenw ni u cɛmancɛ la: Pros, Cons, ani baarakɛcogo ɲumanw .
Batiriw kɔlɔsili fɛɛrɛw ni ɲɔgɔn cɛ ni fanga sɔrɔyɔrɔ kura ye .
Batiriw kɔlɔsili siraw ka ɲɛ cogo min na UPS baarakɛminɛnw kama .