Telefɔni yɔrɔ fanga bɛ jate telefɔni rezow joli ye, k’a sɔrɔ batiri bɛ jate a joli marayɔrɔ ye, o bɛ rezow baaracogo ɲuman lakana. Nka, batiri ladonni kɛra gɛlɛya ye tuma bɛɛ. Ikomi fɛn dilannikɛlaw bɛ ka sɔngɔw jigin ka taa a fɛ sannifeere cɛmancɛ la, batiriw jogo dɔgɔyara kosɛbɛ. San o san, telefɔni kuran sira tiɲɛni 70% ni kɔ bɛ bɔ batiri ko la, o bɛ batiri ladonni kɛ kunkolodimi ye ladonni baarakɛlaw bolo. Nin barokun bɛ batiri tiɲɛni sababu kunbabaw sɛgɛsɛgɛli di, o min bɛ se ka kɛ kunnafoni nafama ye mɔgɔ wɛrɛw bolo.


1. Kuranko minɛn minnu bɛ yɔrɔ la, olu lajɛlen


Kuranminɛn minnu bɛ yɔrɔ la, olu bɛ kɛ ni UPS 40kVA fila ye minnu bɛ bɔ diɲɛ tɔnba dɔ la min lakodɔnnen don kosɛbɛ. Batiriw donna san 2016. Kunnafoni caman bɛ sɔrɔ jukɔrɔ:


UPS Kunnafoni

Batiri kunnafoniw

Marka & Model: Duniya Marka UPS UL33

Marque & Modèle: 12V 100Ah ye

Labɛncogo : 40 kVA, unit 2 bɛ paralɛli la, u kelen-kelen bɛɛ doni bɛ se kW 5 ɲɔgɔn ma

Batiri hakɛ : selilu 30 kulu kelen kɔnɔ, kulu 2, selilu 60 bɛɛ lajɛlen

Baara daminɛ don: san 2006 (san 10 baara)

Baara daminɛ don: 2016 (san 5 baara)


Zuwɛnkalo tile 6, UPS dilannikɛla ye ladonni kɛcogo kɔrɔ kɛ, ka AC ni DC kondansɛriw (san 5 baara) ani fiɲɛbɔlanw falen. Batiri bɔli sɛgɛsɛgɛli senfɛ (miniti 20), a jirala ko batiri bɔli baara kɛcogo man ɲi. Discharge current tun ye 16A ye, ani miniti 10 bɔli kɔfɛ, seli damadɔw ka voltage jigira ka se 11,6V ma, nka batiriw ka wulicogo si ma ye.


A jirala ko UPS batiri kulu fila bɛɛ tun bɛ ni bulging issues ye sɛgɛsɛgɛli senfɛ. U ye baara kɛ ni multimètre ye, ka batiri chargement ripple voltage (a suman ni AC setting ye), o hakɛ tun bɛ se 7V ma (a tɛmɛna ladonni hakɛ kan kosɛbɛ). O de kosɔn, u tun bɛ sigasiga a daminɛ na ko UPS dilannikɛla ka ɛntɛrinɛti injiniyɛriw ye DC filɛri kondansɛri minnu bila u nɔ na, ​​olu tiɲɛna, o kɛra sababu ye ka ripple voltage kojugu UPS ka DC bisi kan, o kɛra sababu ye ka batiri wuli.


2. O yɔrɔ la, dɛsɛko cogoya


Zuluyekalo tile 22, ɲininikɛla ka jɛkulu ye lakana sɛgɛsɛgɛli kɛ tɔnbolofara dɔ la. U y’a ye ko UPS sitɛmu minnu bɛ boon dɔ sankanso 5nan na, olu batiriw tun bɛ ka wuli kosɛbɛ. Ni kuran tigɛra ka bɔ rezow la, siran tun bɛ kɛ ko batiriw tɛ se ka bɔ ka ɲɛ, o bɛ se ka kɛ sababu ye ka kasaara kɛ. O de kosɔn, u y’a fɔ o yɔrɔnin bɛɛ la ko tɔnbolofara ka ladonni baarakɛlaw ka kuma fɛn dilannikɛla ka ɛntɛrinɛti injiniyɛriw fɛ walasa ka sɛgɛsɛgɛli ni gɛlɛyaw ɲɛnabɔ ɲɔgɔn fɛ yɔrɔ la ni mɔgɔ saba bɛɛ ye o dugujɛ wula fɛ.


Bulging of 12V Batiriw

Bulging of 12V Batiriw


Zuluyekalo tile 23 wulada fɛ, mɔgɔ saba sera o yɔrɔ la. Sɛgɛsɛgɛli senfɛ, a jirala ko UPS yɔrɔ fila bɛɛ bɛ baara kɛ cogo bɛnnen na, ni flot voltage ye 404V ɲɔgɔn ye batiriw la (ka bɛn ni paramètres sigilenw ye). A dilabaga ka ɛntɛrinɛti injiniyɛriw ye Fluke 287C multimètre (a tiɲɛniba) kɛ ka batiri chargement ripple voltage suman, o min tun bɛ 0,439V ɲɔgɔn bɔ. Fluke 376 clamp meter (a tiɲɛni ka dɔgɔn) min suman bɛ 0,4V lamini na. Minɛn fila bɛɛ ka jaabiw tun bɛ ɲɔgɔn na, wa u binna ripple voltage dancɛ la min bɛ kɛ minɛnw na (a ka c’a la, a ka dɔgɔ ni 1% ye bus voltage la). O y’a jira ko DC kondansɛri minnu jiginna, olu tun bɛ sariya labato ani ko u tun bɛ baara kɛ cogo bɛnnen na. O la, hakilina min tùn bɛ siga la fɔlɔ ko kondensatɛri caman cili ye ripple voltage (ripple voltage) caya kojugu ani batiri ka bɔgɔbɔgɔli, o ma Sɔ̀rɔ.


Multimètre 0,439V ye

Multimètre: 0,439V ye


Clamp meter bɛ 0,4V ɲɔgɔn kɛ

Kɔlɔsilikɛlan: 0,4V ɲɔgɔn


UPS sitɛmu tariku sɛbɛnw lajɛli y’a jira ko, zuwɛnkalo tile 6, UPS yɔrɔ fila bɛɛ ye batiri bɔli sɛgɛsɛgɛli kɛ miniti 15 kɔnɔ. Kuran sɛgɛsɛgɛlikɛlanba seginni kɔfɛ, miniti 6 chargement equalisé kɛra, o kɔfɛ, miniti 14 batiri bɔli sɛgɛsɛgɛli kɛra a dilabaga ka ɛntɛrinɛti injiniyɛriw fɛ. Kɔrɔbɔli kɔfɛ, UPS sitɛmu ye a yɛrɛma ka charge (sara) naani tugu-tugu ɲɔgɔn na sanga 12 kɔnɔ, ni fasa kelen-kelen bɛɛ bɛ fara ɲɔgɔn kan ni miniti 1 ye, ka ban sɔgɔma 5h32 na zuwɛnkalo tile 9. Kabini o waati, batiriw tora charge (sara) cogo la min bɛ wele ko float.


UPS batiri fɔlɔw sigicogo sɛgɛsɛgɛli wɛrɛ y’a jira ko ninnu ye nin ye:


  • Batiri si hakɛ tun sigilen bɛ kalo 48 (san 4), hali ni batiri 12V si hakɛ yɛrɛ ka kan ka kɛ san 5 ye.

  • Charging equalized tun sigilen bɛ 'enabled.' kan.

  • Charge current dan tun sigilen bɛ 10A kan.

  • Fɛn min bɛ kɛ ka wuli ka taa chargement equalisé la, o bilala 1A la (sistema tun bɛna wuli a yɛrɛma ka taa charge equalized la ni float charge current tɛmɛna 1A kan, hali ni o modeli in nafa fɔlɔ ye 0,03C10~0.05C10 ye, o kɔrɔ ye ko equalized chargement bɛ daminɛ ni float charge current sera 3-5A. Nka, kun dɔnbaliw kosɔn, a dilabaga ka ladonni baarakɛlaw tun y’o ladilan ka kɛ 0,01C10 ye, o kɔrɔ ye ko chargement equalisé bɛna daminɛ ni float charge current sera 1A ma).

  • Sarali lakanani waati min bɛ bɛn ɲɔgɔn ma, o tun bilalen bɛ miniti 720 na (sarali min bɛ bɛn ɲɔgɔn ma, o tun bɛna jɔ a yɛrɛma sanga 12 kɔfɛ).


3. Dɛsɛ sababuw sɛgɛsɛgɛli

Ka da sanfɛla ko kɛlenw kan, dɛsɛ taabolo bɛ se ka sɛgɛsɛgɛ nin cogo in na:


  • O UPS sitɛmu in batiri kulu fila tun bɛ baara la kabini san 4 (12V batiriw ka baara waati ye san 5 ye), wa batiri seko tun dɔgɔyara kosɛbɛ. Nka, sanni a ka tiɲɛ, batiri kɛnɛma cogoya tun bɛ cogo la, a tun tɛ ni taamasiɲɛ si ye min b’a jira ko a bɛ wuli. UPS tariku sɛbɛnw seginnkanni wɛrɛ k’a ta san 2019 zanwuyekalo tile 30 na (sɛbɛn minnu tun bɛ ka kɔn nin don ɲɛ, olu saniyalen don) ka se san 2020 zuwɛnkalo tile 6 ma, o y’a jira ko UPS sitɛmu ye chargement 12 kɛ cogo kelen na, n’a kuntaala jan tɛmɛna miniti 15 kan. O b’a jira ko chargement waati kelen min tun sigilen bɛ UPS sitɛmu kɔnɔ sani a ka ladon, o tun ka surun kosɛbɛ, miniti 15 dɔrɔn, wa UPS sitɛmu ka chargement equalisé waati kunkurunnin tɛna kɛ sababu ye ka batiriw wuli.

  • Ladonni ni kondansɛri caman cili kɔfɛ, UPS sitɛmu daminɛna kokura. Contrôle logique y’a Jira ko batiri in b’a Jira ko a sirilen dòn kokura, o de la a ye miniti 6 chargement equalisé (sarali) daminɛ min bɛ Kɛ kelen ye, o kɔfɛ a y’a Yɛlɛma ka charge (sara) float (float) la. Nka, miniti 14 bɔli sɛgɛsɛgɛli kɔfɛ, UPS sitɛmu ye chargement equalisé daminɛ a yɛrɛma walasa ka batiriw chargement dafalen sɔrɔ. K’a sababu kɛ batiriw tun bɛ baara la san 4 kɔnɔ, u kɔnɔna chargement (sara) marali seko tun tiɲɛna, o kɛra sababu ye ka float charge current (jiri chargeur) tɛmɛn 1A kan, o kɛra sababu ye ka 1A equalized chargement threshold (sarali hakɛ kelen) daminɛ min sigilen bɛ UPS system kɔnɔ (o modeli in nafa fɔlɔ ye 3~5A float charge current ye walasa ka equalized chargement daminɛ, nka kun dɔw la, ladonni baarakɛlaw tun y’o sɛmɛntiya ka kɛ 1A ye). O kɛra sababu ye ka UPS sitɛmu ka chargement equalifié daminɛ siɲɛ caman fo batiri kɔnɔna da wulilen dɔ labanna k’a jɔ (N’o tɛ, UPS sitɛmu tun bɛna t’a fɛ ka charge equalisé segin-segin, o tun bɛ se ka kɛ sababu ye ka batiri kulu tasuma minɛ). O waati kɔnɔna na, batiriw ye chargement cycle naani kɛ minnu bɛ kɛ cogo kelen na sanga 48 kɔnɔ (sɛrɛ kelen-kelen bɛɛ tun bɛ jɔ miniti 1 dɔrɔn sanga 12 o sanga 12 sanni u ka chargement equalize daminɛ kokura). O zarizi kɛcogo kelen kɔfɛ, batiriw labanna ka wuli, wa hali fiɲɛbɔlanw kɛra fɛn tiɲɛnenw ye.


4. Kuncɛli

Ka da kɔlɔsili ni sɛgɛsɛgɛliw kan minnu fɔra sanfɛ, batiri tiɲɛni sababuw ye nin UPS sitɛmu in na:


  • O sababu tilennen tun ye UPS sitɛmu ka chargement paramètres (saracogo) sigicogo jugu ye, o min kɛra sababu ye ka chargement equalisé (sarali kɛcogo kelen) to senna sanga 48 kɔnɔ ni miniti 1 dɔrɔn ye cycle kelen-kelen bɛɛ ni ɲɔgɔn cɛ. Hali batiri kuraw tun tɛna o ɲɔgɔnna chargement equalisé (sarali ɲɔgɔn) janyalen ni fangama muɲu, o bɛ na ni batiri wulicogo tiɲɛni ye o ko la.

  • UPS sitɛmu modɛli ye dilancogo fɔlɔ ye ni baarakɛcogo dantigɛli ye. Nin UPS modɛli kɔrɔ in (min dabɔra a san 20 ye nin ye) tun tɛ ni ' chargement interval protection time equalized' sigicogo ye (a ka c’a la, brand wɛrɛw bɛ o interval sigi tile 7), o kɛra sababu ye ka chargement cycles equalisé caman kɛ ka taa a fɛ.

  • Batiriw ka baara tun Dɔgɔyara k’a sababu Kɛ u si hakɛ ye (san 4 baara la), ni u bɔli seko dɔgɔyara ani u ka charge (sara) maracogo jugu. Sani zuwɛnkalo tile 6 ka se, equalized-to-float-charge conversion current threshold tun sigilen don ka dɔgɔn kosɛbɛ (1A dɔrɔn de bɛ 100Ah batiriw la). UPS sitɛmu nafa fɔlɔ ye 3~5A ye, o bɛɛ n’a ta, ladonni baarakɛlaw y’a sɛmɛntiya cogo la min tɛ se ka ɲɛfɔ ka kɛ 1A ye.

  • UPS sitɛmu tun bɛ baara la kabini san 14, o tɛmɛna a baarakɛbaliya si kan kosɛbɛ, o de y’a to sumani filiw tun tɛ se ka bali. O filiw bɛ se ka kɛ sababu ye ka sistɛmu ka chargement equalisé daminɛ siɲɛ caman k’a sababu kɛ current detection correcte ye.

  • A nisondiyalen don, sɛrɛkili dafalen dɔ min bɛ batiri selilu dɔ kɔnɔ, o ye UPS sitɛmu bali ka t’a fɛ ka chargement cycles equalisées (sarali ɲɔgɔndan) segin-seginw kɛ chargement equalisé naaninan kɔfɛ, o la, batiriw bɛ se ka tasuma minɛ.


5. Fɛɛrɛ minnu bɛ kɛ ka ɲɛsin dɛsɛ ma

Fɛɛrɛ minnu bɛ kɛ walasa ka furakɛli kɛ, olu ye fan fila ye:


Fɔlɔ, aw bɛ UPS batiri chargement paramètres caman sɛmɛntiya waati dɔɔnin kɔnɔ:


  • Aw bɛ chargement equalisé (sarali kɛcogo kelen) bali UPS sitɛmu kɔnɔ.

  • Aw bɛ trigger current ladilan walasa ka wuli ka bɔ float charge la ka taa equalized chargement la ka taa 3A la (hali ni 3A bɛ dɔgɔya dɔɔnin hali bi, bawo default minimum ye 3A ye, nka a tun bilalen bɛ 1A la fɔlɔ).

  • Aw bɛ zarizi lakanani waati min bɛ bɛn ɲɔgɔn ma, aw bɛ o ladilan ka kɛ lɛri 1 ye (a tun bɛ kɛ sanga 12 ye fɔlɔ).


Filanan, tɔnbolofara ye batiri kulu fila ninnu bila batiri kɔkannaw nɔ na, ​​nka batiri kɔkannaw fanga bɛ se ka kɛ Ah 50 dɔrɔn ye, o la sa, u bɛ se ka kɛ waati dɔɔnin dɔrɔn de la kɔrɔtɔko la. Labɛnw bɛ senna walasa ka doni in bɔ UPS sitɛmu la ka taa kuran sɔrɔyɔrɔ wɛrɛw la don nataw la, walasa ka kuran lakanani koɲɛw ɲɛnabɔ ka ɲɛ.


Baarakɛla bɛ musaka caman kɛ san o san UPS sitɛmu ladonni baara la, o bɛɛ n’a ta, ladonni baarakɛlaw ka ɲɛmajɔbaliya n’u ka jateminɛbaliya kosɔn, u yɛrɛ ye fili kɛ ka UPS sitɛmu nafaw sɛmɛntiya, o min tɛ se ka da a la tiɲɛ na. A ka ɲi UPS dilannikɛla k’u ka fɛn dilannenw ladonni ta kosɛbɛ, wa u k’u yɛrɛ tanga o fili jɔnjɔn suguw ma don nataw la, k’u ka ladonni baara kɛcogo ɲɛ. O waati kelen na, a jirala ko baarakɛla fana k’a janto kosɛbɛ ladonni baara nataw la minnu bɛ kɛ UPS dilabaga fɛ, ka jateminɛ kɛcogo dɔ sigi sen kan walasa ka UPS sigida baarakɛcogo ɲɛ ka taa a fɛ min bɛ se ka da a kan.



Aw ye Batiri Jateminɛ sɔrɔ fu

An ka BMS injiniyɛri dɔ bɛna jaabi di sanga 24 kɔnɔ.

(A bɛ se ka kɛ. Fɛɛrɛko kɔrɔtɔlenw dɔrɔn de kama)

An b’i ka gundokow bonya. I ka kunnafoniw bɛna kɛ dɔrɔn ka i ka ɲinini jaabi.

Jɛɲɔgɔnya kɛ ni Anw ye

Fɛn dilannenw ka kulu

Lien teliyalenw

Aw ye ɲɔgɔn sɔrɔ Anw fɛ

   info@dfuntech.com
   +86- 15919182362
  +86-756-6123188

A ka baara kɛcogo ɲɛfɔra 2023 DFUN (ZHUHAI) CO., LTD. Hakɛ bɛɛ bɛ a bolo. Kunnafoni dogolenw maracogo | Sitemap (yɔrɔ karti).