DFPA192-50C2 / DFPA384-50C2
DFUN ezali


-Ba cellules ya pile ya taux ya likolo (Standard): Ekokisaka esengelami ya puissance ya sauvegarde ya tango mokuse ya ≥30 minutes mpe ≥1500 cycles.
-Auto-Start Function: Ezali ko permettre fonctionnement sans pilote na ko restart automatiquement après restauration ya puissance.
-Triple Automatic Protection: Esungaka protection na ba électrodes positifs na négatifs na disjoncteur, ko assurer fidélité ya pile.
-Bopemisi moto na nivo ya PACK (Standard) mpe bopemisi moto na nivo ya armoire (Optional) mpo na bopemisi moto na bosikisiki mpe na mbangu.
-Bomoi ya cycle ya ba cellules ya LiFePO4 : ≥2500 cycles na 1C taux ya charge/décharge, ≥1500 cycles na 4C décharge/0.5C taux ya charge.
-Intégré Smart-Li Battery Monitoring Cloud Platform: Ezali ko assurer fonctionnement mpe entretien ya sécurité mpe efficace, kokitisa ba coûts ya opération ya mokolo na mokolo.
-Modular Design: Ezali ko simplifier installation na configuration ya mbangu; maximum ya 6 armoires en parallèle, kopesa ba options ya temps ya sauvegarde flexible.
Armoire ya Système ya Pile Lithium-ion |
Modèle ya Système ya Pile Li-ion |
DFPA192-50C2.. Ezali na ntina mingi |
DFPA384-50C2.. Ezali na ntina mingi |
Capacité pona système ya UPS |
6-20KVA ezali |
10-40KVA ezali |
|
Tension ya sortie nominale (V) . |
192V |
384V |
|
Modèle ya Module ya Pile |
96V50Ah-2C oyo ezali na kati |
||
Motango ya ba Modules ya Pile (pcs) . |
2pcs ya |
4pcs ya |
|
Capacité ya Cluster ya pile (Ah) . |
50Ah |
||
Puissance ya Cluster ya pile (kWh) . |
9,6kWh |
19,2kWh ya motuka |
|
Max. Courant ya Décharge Constante ya Pile |
100A |
||
Max. Puissance de décharge ya |
19kW ya |
38kW ya |
|
Equalisation ya Tension ya Charge (V) . |
207V |
414V |
|
Tension ya charge flottante (V) . |
204V |
408V |
|
Tension ya décharge ya kokata (V) . |
168V |
336V |
|
Interface ya bopanzi sango |
CAN/RS485/Contact ya kokauka |
||
Bobateli |
Surcharge, Sur-décharge, Sur-temperature, Sur-courant, Court-circuit, etc. |
||
Bolai (LxWxH) . |
600-1000-1000mm |
600-1000-1200mm |
|
Kilo |
Poids ya module XN + Poids ya armoire 120 |
Poids ya module XN + Poids ya armoire 150 |
|
Température ya mosala |
0-40°C (Esengami 20-25°C) |
||