Bi UPS sitɛmu fanba bɛ batiri cogoya kunnafoni sugu dɔw di. Baarakɛlaw bɛ se ka batiri wulicogo, chargement kɛmɛsarada la, baarakɛwaati jateminɛlen, funteni, chargeur cogoya, walima batiri alarma caman ye UPS jiralan walima réseau interface kan. Nin kunnafoniw nafa ka bon, nka a tɛ batiri kelen-kelen bɛɛ cogoya jira tuma bɛɛ kɛnɛma batiri juruba dɔ kɔnɔ.

dɔ Batiri kɔlɔsili sira yɛrɛmahɔrɔnyalen bɛ kɔlɔsili yɔrɔ kɛrɛnkɛrɛnnen dɔ fara batiriw lamini na. Ka kɛɲɛ ni a cogoya ye, a bɛ se ka batiri kelen-kelen bɛɛ ka tension, funteni, kɔnɔna resistance walima impedance, string current, ripple, ambient conditions ani kuntaalajan taabolo suman. O la, danfara tɛ dɔrɔn ni batiri kunnafoniw bɛ sɔrɔ. O ye o kunnafoniw juguya, u ɲɛnabɔli, u tariku ani u waleyacogo ye.

Nin gafe in bɛ UPS ka batiri kɔlɔsili ni BMS yɛrɛmahɔrɔnyalen suma ɲɔgɔn na , wa a b’a ɲɛfɔ waati min na UPS kunnafoniw bɛ se ka dafa, waati min na seli walima bloki yecogo ka kan ka kɛ, ani cogo min na o sigida fila bɛ se ka baara kɛ ɲɔgɔn fɛ.

Nin barokun in kɔnɔ, BMS yɛrɛmahɔrɔnyalen bɛ tali kɛ batiri jɔlen kɔlɔsili siratigɛ la. A man kan ka ɲagami ni lakanani ni kɔrɔsili BMS ye min bɛ don batiri litiyamu-ion kɔnɔ.

UPS batiri kɔlɔsili min bɛ don a kɔnɔ ni i y’a suma ni batiri kɔlɔsili sira yɛrɛmahɔrɔnyalen ye

UPS ka batiri kɔnɔna kɔlɔsili bɛ mun di tuma caman na?

UPS ka kan k’a ka batiri sitɛmu kɔlɔsi walasa a ka se ka chargement kɛ ka ɲɛ, ka backup waati sɔrɔlenw jateminɛ, ka filibaw dɔn, ani ka doni lakana fanga ko dɔ senfɛ. Baara tigitigiw bɛ danfara ka kɛɲɛ ni UPS dilannikɛla, a modɛli, fanga hakɛ, batiri chimie, ani sugandiliw ye minnu sigilen don.

UPS batiri kunnafoniw minnu bɛ sɔrɔ tuma caman na, olu bɛ se ka kɛ ninnu ye:

  • Batiri bɛɛ lajɛlen walima DC bus voltage
  • Batiri charge ani discharge current
  • Batiri charge kɛmɛsarada la walima charge cogoya jateminɛlen
  • Boli waati jateminɛlen sisan doni kɔrɔ
  • Chargeur cogoya ani a baarakɛcogo
  • Batiri walima kabini funteni bɛ bɔ sensɛri kelen walima caman na
  • Batiri min sirilen don, a tigɛlen don, a barika ka dɔgɔ, walima a bɛ wuli ka bɔ a nɔ na
  • Batiri sɛgɛsɛgɛli min kɛra otomatiki la walima min daminɛna ni bolo ye, o jaabiw

Nin kunnafoni minnu bɛ sɔrɔ sistɛmu kɔnɔ, olu bɛ baarakɛlaw dɛmɛ u k’a faamu ni UPS batiri sɔrɔyɔrɔ bɛ ɲɔgɔn na, ni a bɛ charge (sara), ni a bɛ bɔli kɛ, walima ni a bɛ gɛrɛ baarakɛcogo danba dɔ la. Nafa b’a la fana yɔrɔjan UPS kɔlɔsili la SNMP fɛ, ɛntɛrinɛti ɲɛnabɔli karti fɛ, DCIM fɛ, BMS fɛ, walima baarakɛyɔrɔ wɛrɛ fɛ.

Nka, juru bɛɛ lajɛlen wulicogo nɔgɔman tɛ a jira ko juru kɔnɔ batiri bɛɛ kɛnɛman don. Bloki barikama kelen bɛ se ka masɔrɔ batiri tɔw fɛ flot baara waati, kɛrɛnkɛrɛnnenya la ni tension bɛɛ lajɛlen ni batiri cogoya bɛɛ dɔrɔn de bɛ sɔrɔ.

Batiri kɔlɔsili sira yɛrɛmahɔrɔnyalen ye mun ye?

Batiri kɔlɔsili sira yɛrɛmahɔrɔnyalen dɔ sigilen don kɛrɛnkɛrɛnnenya la walasa ka batiri cogoya kunnafoniw lajɛ ani k’u sɛgɛsɛgɛ. Sensɔrɔlanw bɛ siri seli kelen-kelen bɛɛ la walima batiri blokiw la, k’a sɔrɔ juru-ni-minɛnw bɛ sisan ni fɛn wɛrɛw suman minnu bɛ tila ɲɔgɔn na. Kontrɔla walima dakun dɔ bɛ kunnafoniw mara, ka alarmaw lawuli, ka kunnafoni sugandilenw bila sigida walima cɛmancɛ ɲɛmɔgɔyaso la.

Ka kɛɲɛ ni batiri suguya ni sistɛmu dilanni ye, BMS yɛrɛmahɔrɔnyalen bɛ se ka nin kɔlɔsi:

  • Seli kelen-kelen bɛɛ walima bloki tension
  • Batiri kelen-kelen bɛɛ dakun walima a kɔnɔna funteni
  • Kɔnɔna rezisti, impedansi, walima ohm hakɛ wɛrɛw
  • String voltage (Sɔrɔ tension) ye
  • Float, charge ani discharge current ye
  • Ripple voltage ani ripple current
  • Lamini funteni ni nɛnɛ
  • Insulasi resistance, leakage, walima a kɛcogo kɛrɛnkɛrɛnnen paramɛtiri wɛrɛw
  • Tariku taabolo, bɔli sɛbɛnw, ani alarma tariku

nafaba min bɛ o la , o ye filiw sigiyɔrɔmali ye . Sani a ka batiri alarma caman dɔrɔn sɔrɔ, baarakɛla bɛ se ka yɔrɔ min tɔɔrɔlen don, UPS, juru ani batiri jɔyɔrɔ dɔn ani ka segin a sumanikɛlanw yeli cogo min na waati tɛmɛnen kɔfɛ.

UPS Kɔlɔsili jɔlen ni BMS yɛrɛmahɔrɔnyalen: Danfara jɔnjɔnw

1. Sumanikɛlan hakɛ

UPS kɔnɔna kɔlɔsili bɛ sinsin batiri sitɛmu dafalen kan tuma caman na bawo UPS ka kan ka chargement, dischargement, runtime ani protection ɲɛnabɔ. BMS yɛrɛmahɔrɔnyalen dɔ dabɔra walasa ka seli walima bloki-dakun yecogo fara a kan ka fara juru sumani caman kan.

Nin ye danfara ye min bɛ kɛ mɔgɔw bɛɛ fɛ, a tɛ diɲɛ bɛɛ ka sariya ye. UPS sitɛmu modulu dɔw, batiri hakilitigiw, ani litiyamu-ion sitɛmu dɔw bɛ se ka modulu kelen-kelen walima selilu kɔlɔsi. O la, porozɛ jɛkulu ka kan ka kunnafonidilanw lisɛli yɛrɛ sɛgɛsɛgɛ sanni u ka jateminɛ kɛ ko ɲɛnabɔli bɛ sɔrɔ ka bɔ daɲɛw la 'batiri kɔlɔsili min bɛ don a kɔnɔ.'

2. Se ka batiri barikama dɔ sɔrɔ

UPS bɛ se ka batiri barikama fɔ, baarakɛwaati dɔgɔyara, walima yɛrɛsɛgɛsɛgɛli dɛsɛlen k’a sɔrɔ a ma batiri kɛrɛnkɛrɛnnen dɔn min bɛ o ko ɲɛnabɔ. BMS yɛrɛmahɔrɔnyalen min bɛ selilɛri sanfɛ, o bɛ se ka mɔgɔ kelen-kelen bɛɛ ka tension, funteni ani rezisti taabolo suma ani ka ladonni baarakɛlaw jira batiri jɔyɔrɔ tigitigi la min ka kan ka sɛgɛsɛgɛli kɛ.

Yɔrɔ tigitigiw nafa ka bon kosɛbɛ ni kɛnɛma batiriw ni juruw paralɛliw hakɛ bɛ caya.

3. Tariku kunnafoniw ni taabolo sɛgɛsɛgɛli

UPS ko kɛlenw sɛbɛnw dabɔra fɔlɔ UPS baarakɛcogo lamini na. U bɛ se ka fɛnw jiginni, batiri sɛgɛsɛgɛliw, chargeur alarmes, batiri dɔgɔyali ko kɛlenw, ani baarakɛcogo kunnafoniw sɛbɛn. Dugukolo juguya ni a mara waati bɛ bɔ UPS ni ɲɛnabɔli porogaramuw de la.

Kɔlɔsili-yɔrɔ yɛrɛmahɔrɔnyalen dɔ sinsinnen bɛ batiri tariku kan. A bɛ se ka sumanikɛlanw mara batiri kelen-kelen bɛɛ la, ka sisan nafaw suma ni basigi sigilenw ye, ka deviation jira juru kelen kɔnɔ, ani ka fɛn caman lajɛ fɛn caman Changements de flot, discharge ani recharge cogoyaw la.

4. Alarm ka kunnafoni

UPS alarma général b’a fɔ baarakɛla ye ko a ka kan ka jateminɛ kɛ. Batiri alarma kɛrɛnkɛrɛnnen ka kan ka yɔrɔ min tɔɔrɔlen don, o sɛrɛkili, batiri nimɔrɔ, paramɛtiri, nafa sumanlen, dan sigilen, waati ani waati janya di. Dakun caman, delay, recovery logic, ani rate-of-change analysis bɛ se ka dɛmɛ ka dɔ bɔ nuisance alarmes la.

5. Yɛrɛmahɔrɔnya ka bɔ UPS Plateforme la

Kɔlɔsili min bɛ don a kɔnɔ, o ye UPS ka ɲɛnamaya kɛcogo sugandilen dɔ ye. Donanw sɔrɔli, u bonya, u ka porogaramuw ani u ka kumaɲɔgɔnya suganditaw bɛ bɔ o yɔrɔ de la.

BMS yɛrɛmahɔrɔnyalen bɛ se ka batiriw sigicogo kɔlɔsi UPS taamasiyɛn suguya caman kɔnɔ, wa a bɛ se ka kɛ sababu ye ka ɲɔgɔndan kelen di minɛn ɲagaminenw kulu ma. O nafa ka bon yɔrɔw la minnu bɛ UPS modɛli caman baara, boon caman, walima kɔlɔsilikɛyɔrɔ cɛmancɛ la.

6. Ladonni sinsinnan

UPS kɔlɔsili bɛ fanga sɔrɔcogo dafalen baara dɛmɛ. Kɔlɔsili yɛrɛmahɔrɔnyalen bɛ batiri ladonni dɛmɛ min sinsinnen bɛ cogoya kan. A bɛ ekipuw dɛmɛ u k’a latigɛ batiri minnu ka kan ka sɛgɛsɛgɛli kɛ, ka segin u kan, ka ɲɔgɔndan sɛgɛsɛgɛli kɛ, walima ka jateminɛ kɛ u falenni na.

7. Seko ni dɔnko sɛgɛsɛgɛli

UPS cogoya jiralan camanba walima batiri kɔlɔsili kɛcogo kɔrɔ si tɛ batiri juru dɔ ka ampere-lɛrɛ seko sɔrɔlen jira a yɛrɛma. Voltage, temperature, current ani resistance bɛ cogoya jiralan nafamaw di, ka sɔrɔ seko walima boli waati sɛgɛsɛgɛli bɛnnen bɛ baarakɛcogo sɛgɛsɛgɛ bɔli cogoya ɲɛfɔlenw kɔnɔ.

UPS sitɛmu dɔw bɛ batiri sɛgɛsɛgɛli kɛ otomatiki la, nka sɛgɛsɛgɛli kɛcogo, a doni, a kuntaala ani a sɛgɛsɛgɛli kɛcogo ka kan ka lajɛ. Fɛn minnu nafa ka bon hali bi, olu bɛ se ka kɛ sababu ye ka u seko sɛgɛsɛgɛ tuma ni tuma ka kɛɲɛ ni batiri dilabaga ye, ka kɛɲɛ ni a ladonni sariya ye, ani sariyaw ye minnu bɛ sirataama.

UPS sitɛmu-dakun batiri kunnafoniw ni yɛrɛmahɔrɔnya selilɛri-ni kɔlɔsili kunnafoniw sumalen

Tuma jumɛn na UPS ka kɔlɔsili jɔlen bɛ se ka se ka kɛ?

Kɔlɔsili min bɛ don a kɔnɔ, o bɛ se ka kɛ ko bɛnnen ye ni batiri sitɛmu ka dɔgɔ, ni farati ka dɔgɔ, ani ni ladonni fɛɛrɛ sinsinnen bɛ batiri dafalen caman cili kan sanni ka batiri kelen-kelen bɛɛ falen.

Misali dɔw bɛ se ka kɛ:

  • UPS sitɛmu misɛnnin minnu bɛ kɛ fasa kelen na, minnu bɛ ni izini batiriw ye
  • Baarakɛcogo minnu na batiri modulu dafalen bɛ wuli ka kɛ fɛn kelen ye
  • Yɔrɔ minnu bɛ kɛ ni fɛn caman cili waati kunkurunnin ye ani sɛgɛsɛgɛli bɛ kɛ tuma bɛɛ yɔrɔ la
  • Doni minnu tɛ gɛlɛn ye, batiri tiɲɛni bɛ se ka baara kɛ yɔrɔ minnu na
  • UPS sitɛmu minnu bɛ modulu walima selilɛri hakɛ sumanikɛlanw, tariku ani alarmaw wajibiyalenw di kaban

O latigɛ ka kan ka sinsin baarakɛcogo sɛgɛsɛgɛlenw kan, a man kan ka sinsin batiri ɲɛ dɔ sɔrɔli dɔrɔn kan UPS jiralan kan. Aw ye ɲininkali kɛ paramɛtiri minnu bɛ suman, sensɛriw bɛ yɔrɔ min na, ni batiri kelen-kelen bɛɛ bɛ se ka dɔn, kunnafoniw bɛ mara waati joli kɔnɔ, ani kunnafoni jumɛnw bɛ sɔrɔ kumaɲɔgɔnya sira fɛ.

Batiri kɔlɔsili sira yɛrɛmahɔrɔnyalen bɛ nafa sɔrɔ kosɛbɛ ni batiri tiɲɛni bɛ se ka baara gɛlɛn dɔ tigɛ walima ni batiri sigili ka bon kojugu fo a tɛ se ka ɲɛnabɔ ka ɲɛ bolola sɛgɛsɛgɛli fɛ ani UPS alarma caman fɛ.

Kun minnu ka teli ka kɛ walasa ka yɛrɛmahɔrɔnya kɔlɔsili fara a kan, olu ye:

  • UPS sitɛmu belebelebaw minnu bɛ fasa saba la ni kɛnɛma VRLA batiri juruw ye
  • Batiri juru caman minnu bɛ taa ɲɔgɔn fɛ walima batiri kelen-kelen kɛmɛ caman
  • Donanw, dɔgɔtɔrɔsow, wariko yɔrɔw, iziniw, bolifɛnw, ani baara nafama wɛrɛw
  • Wajibiya min bɛ kɛ walasa ka batiri barikama tigitigi dɔn sani juru dafalen ka nɔ bila
  • Mako bɛ mɔgɔ kelen-kelen bɛɛ ka tension, funteni ani resistance cogoyaw la
  • Batiri so minnu tɛ kɔlɔsi walima yɔrɔjan yɔrɔ minnu na
  • Kɔlɔsili cɛmancɛ la UPS taamasiyɛn caman kɔnɔ, sow, walima yɔrɔ caman na
  • Jɛɲɔgɔnya ni DCIM, BMS, EPMS, SCADA, walima ɛntɛrinɛti baarakɛyɔrɔ dɔ ye
  • Ladonni sariya minnu bɛ sɛbɛnni caman wajibiya, ka bɔli minɛ, ani alarma tariku

Kɔlɔsili yɛrɛmahɔrɔnyalen tɛ sɛgɛsɛgɛliw nɔnabila ye, ɲɔgɔndan ladonni, chargeur sɛgɛsɛgɛli, fiɲɛbɔli, walima seko sɛgɛsɛgɛli. A kun ye ka yecogo ɲɛ ani ka ladonni kɛ laɲini ye ka ɲɛ.

Yala UPS kɔlɔsili ni BMS yɛrɛmahɔrɔnyalen bɛ se ka baara kɛ ɲɔgɔn fɛ wa?

Awɔ. Seko ni dɔnko siratigɛ kɔrɔlen caman na, o sɔrɔyɔrɔ fila bɛ ɲɔgɔn dafa.

UPS bɛ baarakɛcogo ɲɛfɔ i n’a fɔ:

  • Donni, bɔli, bypass, ani doni cogoya
  • UPS baarakɛcogo
  • Chargeur cogoya
  • Batiri bɔli ko kɛlen
  • Boli waati jateminɛlen
  • UPS caman ani batiri alarmaw

BMS yɛrɛmahɔrɔnyalen bɛ batiri kɛrɛnkɛrɛnnenw kunnafoni di i n’a fɔ:

  • Batiri kelen-kelen bɛɛ dɔnni
  • Voltage (voltaji) tilatilali ka tɛmɛn jiribolo kan
  • Funteni danfara bɛ batiriw ni ɲɔgɔn cɛ
  • Resistance walima impedance (kɛlɛli) taabolo
  • String current ani ripple kɛcogo
  • Batiri hakɛ alarma ani ladonni tariku

Ni o sitɛmu fila bɛɛ donna DCIM, BMS, EPMS, SCADA, walima ɲɛnabɔli yɔrɔ wɛrɛ la, baarakɛlaw bɛ se ka batiri tiɲɛni dɔ siri UPS baarakɛcogo la. Misali la, tension (voltaji) jiginni waati la, o bɛ se ka lajɛ ɲɔgɔn fɛ ni doni, kuran, boli waati ani chargeur kunnafoniw ye.

UPS ani batiri kɔlɔsili sira yɛrɛmahɔrɔnyalen min bɛ ɲɔgɔn sɔrɔ ni DCIM walima yɔrɔw ɲɛnabɔli yɔrɔ ye

Ɲininkali minnu ka kan ka kɛ sani i ka i jigi da UPS Built-in Monitoring kan

  1. Yala UPS bɛ juru dafalen kɔlɔsi, batiri modulu kelen-kelen bɛɛ, walima batiri kelen-kelen bɛɛ wa?
  2. Paramɛtiri jumɛnw bɛ suman k’a ɲɛsin u yɛrɛ ma, ani nafa jumɛnw bɛ jate?
  3. Batiri funteni jateminɛnan joli bɛ sigi, ani u bɛ min?
  4. Yala o sitɛmu bɛ se ka batiri barikama dɔ dɔn ni juru ni a jɔyɔrɔ ye wa?
  5. Yala mɔgɔ kelen-kelen bɛɛ ka tension ni resistance trends bɛ mara wa?
  6. Batiri kunnafoni jumɛnw bɛ sɔrɔ SNMP, Modbus walima protocol wɛrɛ fɛ?
  7. Sumanikɛlanw, alarmaw ani bɔli ko kɛlenw bɛ mara waati joli kɔnɔ?
  8. Yala o sitɛmu bɛ se ka kɛnɛma batiri kabiniw kɔlɔsi ani fɛn minnu bɛna bonya sini wa?
  9. Yala a bɛ se ka UPS taamasiyɛn walima yɔrɔ caman fara ɲɔgɔn kan plateforme kelen kɔnɔ wa?
  10. Yala batiri sɛgɛsɛgɛli bɛ se ka a seko yɛrɛ sɛgɛsɛgɛ wa, walima batiri baarakɛcogo bɛɛ lajɛlen dɔrɔn?

DFUN bɛ UPS batiri kɔlɔsili yɛrɛmahɔrɔnyalen dɛmɛ cogo min na

DFUN batiri kɔlɔsili fɛɛrɛw dabɔra walasa ka batiri yecogo basigilen fara UPS ni fanga baarakɛcogo kɔrɔw kan. Labɛn minnu bɛ sɔrɔ, olu bɛ se ka batiri sensɛri kelen-kelenw, juru sumanikɛlanw, kunnafonisɛbɛnw, dakunw, sigida jiralanw, ani ɲɛnabɔli porogaramuw fara ɲɔgɔn kan.

Ka kɛɲɛ ni fɛnɲɛnɛma ni batiri cogoya sugandilenw ye, o sitɛmu bɛ se ka mɔgɔ kelen-kelen bɛɛ ka tension, funteni, resistance walima impedance, string voltage, current, ripple, ambient conditions, SOC, SOH ani fɛn wɛrɛw kɔlɔsi minnu ka kan. Tariku kurukuruw, alarma sɛbɛnw, bɔli kunnafoniw, ani yɔrɔjan kunnafoniw, olu bɛ baarakɛlaw dɛmɛ u ka sɛgɛsɛgɛli kɛ fɛn wɛrɛw la minnu bɛ ka yiriwa ani ka ladonni bila jɔyɔrɔ fɔlɔ la.

Kumaɲɔgɔnya suganditaw bɛ se ka dɛmɛ don jɛɲɔgɔnya la ni yɔrɔw sigicogo kɔrɔw ye. A jɔcogo bɛnnen bɛ bɔ batiriw ka kemikaliya la, bloki wulicogo la, juru hakɛ la, batiri hakɛ la, UPS labɛncogo la, kumaɲɔgɔnya kɛcogo la, ani yɔrɔ lamini na.

DFUN yɛrɛmahɔrɔnyalen UPS batiri kɔlɔsili sira ni selilɛri sensɛriw ɲɛnabɔbaga ani kɔlɔsili porogaramu

Ɲininkali minnu bɛ kɛ tuma caman na

Yala UPS ka batiri kɔlɔsili ni BMS kɛrɛnkɛrɛnnen ye kelen ye wa?

A tɛ kɛ wajibi ye. UPS kɔlɔsili dabɔra fɔlɔ walasa ka UPS sitɛmu baara ani k’a lakana. Batiri kɔlɔsili sira kɛrɛnkɛrɛnnen dɔ bɛ sinsin batiri sumanikɛcogo caman kan, mɔgɔ kelen-kelen bɛɛ ka filiw sigiyɔrɔmali, tariku, ani ladonni sɛgɛsɛgɛli. UPS walima batiri hakilitigi dɔw bɛ se ka baara kɛ ni o baara suguw ye, o la, kunnafoni yɔrɔ lakikaw ka kan ka sɛgɛsɛgɛ.

Yala UPS bɛ se ka batiri barikama kelen dɔn juru jan kɔnɔ wa?

Sitimɛ dɔw bɛ se ka modulu barikama dɔ dɔn, nka UPS plateforme caman bɛ batiri alarmaw dɔrɔn de di minnu bɛ kɛ ni sɛrɛkili ye walima minnu bɛ kɛ fɛn bɛɛ ye. Sensɔrɔlanw ka kan ka kɛ selilɛri walima bloki hakɛ la ni poroze bɛ batiri jɔyɔrɔ tigitigi dɔnni de wajibiya.

Yala BMS yɛrɛmahɔrɔnyalen dɔ bɛ UPS ɲɛminɛ wa?

Batiri kɔlɔsili sira jɔlen bɛ kunnafoniw lajɛ tuma caman na ani ka alarmaw lawuli. A bɛ se ka kunnafoniw falenfalen ni UPS walima baarakɛyɔrɔ plateforme ye, nka a tɛ UPS kunnafoni a yɛrɛma fo ni porozɛ in dabɔra kɛrɛnkɛrɛnnenya la o baara kama.

Yala BMS yɛrɛmahɔrɔnyalen bɛ se ka baara kɛ ni DCIM walima BMS platform kelen ye ni UPS ye wa?

Ɔwɔ, ni kumaɲɔgɔnya protocole ni data points wajibiyalenw bɛ dɛmɛ. UPS ni batiri kɔlɔsili kunnafoniw bɛ se ka bila DCIM, sow ɲɛnabɔli, EPMS, SCADA, walima sigida wɛrɛ la.

Yala batiri kɔlɔsili bɛ UPS batiri sɛgɛsɛgɛli nɔ bila wa?

Ayi, kɔlɔsili min bɛ to senna, o bɛ sumani kɛcogo juguw ni tiɲɛni kɛcogo jira. Seko walima boli waati sɛgɛsɛgɛli bɛ batiri baara cogo sɛgɛsɛgɛ a bɔli cogoya ɲɛfɔlenw na. Ladonni porogaramu kɔrɔlenw ka teli ka baara kɛ ni o fila bɛɛ ye.

Yala BMS yɛrɛmahɔrɔnyalen bɛ VRLA batiriw dɔrɔn de kama wa?

Ayi, kɔlɔsili fɛɛrɛw bɛ se ka VRLA, plɔmu-asidi ji la, Ni-Cd, ani batiri jɔlen wɛrɛw dɛmɛ. Bɛnkan ka kan ka dafa chimie lakika, tension nominal, ani paramètres wajibiyalenw na.

Aw ye kɔlɔsili hakɛ bɛnnen dɔn aw ka UPS batiriw la

Desizɔn ɲuman bɛ bɔ batiri tiɲɛni kɔlɔlɔ la ani yecogo min bɛ sɔrɔ kaban UPS fɛ. Aw ye aw ka UPS modɛli ci DFUN ma, batiri chimie, batiri wulicogo, batiri ni juru hakɛ, kumaɲɔgɔnya yɔrɔ min bɛ yen, paramɛtiriw wajibiyalenw, ani ɲɛnabɔli yɔrɔ. An ka ɛntɛrinɛti jɛkulu bɛ se ka dɛmɛ don k’a dɔn ni kɔlɔsili wɛrɛw bɛ kɛ selilɛri hakɛ la, o bɛnnen don i ka baarakɛcogo ma.

Aw ye Batiri Jateminɛ sɔrɔ fu

An ka BMS injiniyɛri dɔ bɛna jaabi di sanga 24 kɔnɔ.

(A bɛ se ka kɛ. Fɛɛrɛko kɔrɔtɔlenw dɔrɔn de kama)

An b’i ka gundokow bonya. I ka kunnafoniw bɛna kɛ dɔrɔn ka i ka ɲinini jaabi.

Jɛɲɔgɔnya kɛ ni Anw ye

Fɛn dilannenw ka kulu

Lien teliyalenw

Aw ye ɲɔgɔn sɔrɔ Anw fɛ

   +86- 15919182362 ye
  +86-756-6123188 ye

A ka baara kɛcogo ɲɛfɔra 2023 DFUN (ZHUHAI) CO., LTD. Hakɛ bɛɛ bɛ a bolo. Kunnafoni dogolenw maracogo | Sitemap (yɔrɔ karti).