Desain terpadu: sistem 48V DC nggabungake modul penyearah, unit pemantauan, unit distribusi daya, baterei, lan kabeh ing siji
Baterei lithium cerdas: Baterei lithium cerdas ndhukung campuran baterei anyar lan lawas lan baterei timbal-lithium, lan nduweni fungsi dorongan cerdas kanggo nyukupi kabutuhan sumber daya remot 5G
Desain daya dhuwur: nganti 600A (36KW)
Dhukungan kapasitas dhuwur: Ndhukung nganti 10 klompok baterei lithium cerdas 48V100AH utawa 48V165AH
Dhukungan input multi-energi: Ndhukung listrik, solar, lan solar.
Ndhukung sawetara lemantun sistem ing podo karo: nambah daya output
Ndhukung sawetara mode panyimpenan energi: mode cukur puncak, mode regulasi puncak, lsp.
Panggonan cadangan kanggo instalasi peralatan komunikasi
Jinis Solusi |
Solusi 1 (Njaba) |
Solusi 2 (Ing njero ruangan) |
|
produk Jinis |
DFCA48-O-XXX-XXX-X |
DFCA48-I-XXX-XXX-X |
|
Sistem |
Ukuran (W × D × H) |
700mm × 800mm × 2200mm |
600-800-2000mm |
Bobot |
<256 kg (tanpa modul rectifier, baterei, peralatan opsional liyane) |
< 200 kg (tanpa modul rectifier, baterei, peralatan opsional liyane) |
|
Mode Instalasi |
Pemasangan Ground (Outdoor) |
njero ruangan |
|
kabel Mode |
Saka ngisor |
Saka ngisor utawa ndhuwur |
|
pangopènan Mode |
Saka ngarep |
Saka ngarep lan mburi |
|
Kabinet Kab Bahan |
SGCC galvanis sheet karo resistance karat kuwat |
SPCC kualitas dhuwur cold rolled steel plate |
|
kabinet Warna |
Werna abu-abu: RAL 7035 |
Werna abu-abu: RAL9007 |
|
Grounding Bar |
7×M6,1×M8 |
||
EMC |
EN 300386 Kelas A |
||
Tingkat pangayoman |
IP55 |
IP20 |
|
Baterei |
njero Rak & Spasi |
3U, rak 19-inci (miturut konfigurasi nyata) |
|
Jinis baterei |
Maks. 10 lembar DFPA48100-S/DFPA48165-S |
||
Mode pendinginan |
AC AC |
DC48V 1000W |
NO |
PDistribusi Unit |
AC Input |
220/384Vac telung fase papat kawat, kompatibel karo fase tunggal telung fase: 200-240 Vac/346-415 Vac fase tunggal: 200-240Vac, dukungan kanggo input generator diesel |
|
ATS Tipe |
ATS-63A1/ATS-63A2/ATS-125C1 (opsional, mung kanggo rong input AC) |
||
PV Input |
Tegangan Input: 102V (rentang 70-150V), Kapasitas Input 63A/2P * 4 |
||
DC Output |
Tegangan: Mode Normal: 42VDC-58VDC, Modul Boost: 53.5VDC kanggo ndhukung konstanta 57VDC (kudu dipasang nganggo Baterei Lithium Smart) |
||
Arus Max.36kW(600A) |
|||
Cabang Baterei |
MCB: 125A × 10 |
||
Cabang LLVD |
2×125AMCB,3×63AMCB (LLVD1) |
||
BLVD Cabang |
2×32AMCB,2×40AMCB,4×63AMCB ,4×63AMCB ,2×125AMCB |
||
SP D |
Input AC:: 40kA (8/20μs) |
||
Output DC: 20 kA/maks=40KA, 8/20 μ |
|||
Rectifier |
Input / Output |
Input 85-300VAC; Output 42-58VDC; Daya 3000W, maksimal 12 konfigurasi |
|
PV Modul |
Input / Output |
Tegangan Input: DC70-150V Output: 3000W(0-62.5A@-42Vdcto-58Vdc): efisiensi ≥ 0.96 (opsional) |
|
Ngawasi |
Konfigurasi Antarmuka |
Input DI: DI*6, output DO: DO*6, Antarmuka komunikasi: RS485*1, LAN*1 |
|
Lingkungan |
operasi Suhu |
0ºC nganti +45ºC + radiasi surya (ndhukung -20ºC yen dikonfigurasi kothak pra-panas)) |
|
Suhu panyimpenan |
-40 ℃ ~ + 70 ℃ |
-20 ℃ ~ + 60 ℃ |
|
Operasi Relatif Kelembapan |
5% nganti 95% (ora ana kondensasi) |
||
Altitude |
0 nganti 4000 m (1ºC saben 200 m suhu mudhun saka 2000 nganti 4000 m) |
||