| A awm theihna: | |
|---|---|
| A zat: | |


Integrated design: 48V DC system hmanga rectifier module, monitoring unit, power distribution unit, battery, leh pakhata dah vek a ni
Smart lithium battery: Smart lithium battery hian battery thar leh hlui leh lead-lithium battery mixing a support a, 5G remote power supply mamawh phuhruk turin intelligent boost function a nei bawk
Power sang tak design: 600A(36KW) thleng a ni.
High-capacity support: 48V100AH emaw 48V165AH smart lithium battery group 10 thleng support
Multi-energy input support: Mains, diesel, leh solar te a support thei.
System cabinet tam tak parallel-a support: output power tihpun
Energy dahkhawmna mode hrang hrang a support: peak shaving mode, peak regulation mode, etc.
Inbiakpawhna hmanrua dahna tur hmun reserve
Solution chi hrang hrang |
Solution 1 (Pawn lam) 1.1. |
Hrehawmna chinfel dan 2 (Indoor) . |
|
Product chi hrang hrang |
DFCA48-O-XXX-XXX-X hmanga tihchhuah a ni |
DFCA48-I-XXX-XXX-X hmanga tihchhuah a ni |
|
Tihdan |
A zau zawng (W × D × H) 1.1. |
700mm×800mm×2200mm a ni |
600-800-2000mm inkar a ni |
Buk |
< 256 kg (rectifier module, battery, hmanraw dang duhthlan tur awm lo) |
< 200 kg (rectifier module, battery, hmanraw dang duhthlan tur awm lo) |
|
Installation Mode a ni |
Leia dah (Pawn lam) . |
Indoor chhungah |
|
Cabling Mode hmanga siam a ni |
A hnuai lam atang chuan |
A hnuai lam atang emaw, chunglam atang emaw |
|
Maintenance Mode a ni |
Hma lam atang chuan |
Hma leh hnung lam atang chuan |
|
Cabinet Material a ni |
SGCC galvanized sheet a ni a, corrosion resistance chak tak a nei bawk |
SPCC quality tha tak, cold rolled steel plate a ni |
|
Cabinet rawng a ni |
A dum hring: RAL 7035 |
A dum hring:RAL9007 |
|
Grounding Bar a ni |
7×M6,1×M8 a ni |
||
EMC a ni |
EN300386 Class A atanga lo chhuak a ni |
||
Hriselna Level |
IP55 a ni |
IP20 a ni |
|
Battery |
Inner Rack & Space a awm bawk |
3U, 19-inch rack (configuration tak tak angin) a ni. |
|
Battery chi hrang hrang |
Max. 10pcs DFPA48100-S/DFPA48165-S a ni a, a man pawh a tlawm hle |
||
Cooling Mode a ni |
DC Air Conditioner a awm bawk |
DC48V 1000W a ni |
AIH |
P ower sem chhuahna unit |
AC Input a ni |
220/384Vac three-phase four-wire, single-phase three-phase nena inmil: 200-240 Vac/346-415 Vac single- phase: 200-240Vac, diesel generator inputs support |
|
ATS Type a ni |
ATS-63A1/ATS-63A2/ATS-125C1 (a duh chuan, AC input pahnih tan chauh) |
||
PV Input a ni |
Input Voltage: 102V (range 70-150V) , Input theihna 63A/2P*4 a ni |
||
DC Output a ni |
Voltage:Normal Mode: 42VDC-58VDC, Boost Module: 57VDC constant support turin 53.5VDC (Smart Lithium Battery hmanga install tur a ni) |
||
Tunah hian Max.36kW(600A) a ni. |
|||
Battery Branch a ni |
MCB:125A×10 a ni |
||
LLVD Branch a ni |
2×125AMCB,3×63AMCB (LLVD1) a ni a, a man pawh a tlawm hle. |
||
BLVD Branch a ni |
2×32AMCB,2×40AMCB,4×63AMCB,4×63AMCB,2×125AMCB a ni |
||
SP D |
AC Input::40kA(8/20μs) a ni a, a man pawh a tlawm hle. |
||
DC atanga chhuak: 20 kA/max=40KA,8/20 μ |
|||
Rectifier a ni |
Input/Output a ni |
Input 85-300VAC;Output 42-58VDC;Power 3000W, a tam ber chu configuration 12 a ni |
|
PV a ni Module a ni |
Input/Output a ni |
A chhuahna tur voltage: DC70-150V A chhuahna: 3000W( 0-62.5A@-42Vdcto-58Vdc): efficiency ≥ 0.96 (a duh chuan) |
|
Monitoring neih a ni |
Interface siam dan tur |
DI input: DI*6, DO output: DO*6, Inbiakpawhna interface: RS485*1, LAN*1 |
|
Chenna khawvel |
Operating Temperature a ni |
0oC atanga +45oC + ni zung (pre-heat box configure a nih chuan -20oC support)) |
|
A dahna Temperature a ni |
–40°C ~ +70°C a ni |
–20°C ~ +60°C a ni |
|
A hnathawhna hmun Relative Humidity |
5% atanga 95% (condensation awm lo) . |
||
Altitude a ni |
0 atanga 4000 m (2000 atanga 4000 m atanga 200 m temperature tlahniam) ah 1oC a ni. |
||