| Muaj: | |
|---|---|
| Quantity: | |


Integrated tsim: 48V DC system integrating rectifier module, xyuas chav tsev, fais fab faib chav tsev, roj teeb, thiab tag nrho nyob rau hauv ib tug
Smart lithium roj teeb: Lub roj teeb lithium ntse txhawb kev sib xyaw ntawm cov roj teeb tshiab thiab qub thiab cov roj teeb lead-lithium, thiab muaj lub zog ua kom muaj peev xwm ua tau raws li qhov xav tau ntawm 5G tej thaj chaw deb fais fab mov
Kev tsim hluav taws xob siab: mus txog 600A (36KW)
Kev them nyiaj yug muaj peev xwm: Txhawb txog li 10 pawg ntawm 48V100AH lossis 48V165AH ntse lithium roj teeb
Kev them nyiaj yug Multi-zog input: Txhawb mains, diesel, thiab hnub ci.
Txhawb ntau qhov system txee nyob rau hauv parallel: nce zog tso zis
Txhawb ntau lub zog cia hom: ncov shaving hom, ncov tswj hom, thiab lwm yam.
Khaws qhov chaw rau kev teeb tsa cov khoom siv sib txuas lus
Hom tshuaj |
Txoj Kev 1 (Sab nraum zoov) |
Kev daws 2 (hauv tsev) |
|
Yam khoom |
DFCA48-O-XXX-XXX-X |
DFCA48-I-XXX-XXX-X |
|
Qhov system |
Qhov Loj (W × D × H) |
700mm × 800mm × 2200mm |
600-800-2000 hli |
Qhov hnyav |
<256 kg (tsis muaj rectifier modules, roj teeb, lwm yam khoom siv yeem) |
<200 kg (tsis muaj rectifier modules, roj teeb, lwm yam khoom siv yeem) |
|
Kev teeb tsa hom |
Kev teeb tsa hauv av (Sab nraum zoov) |
Sab hauv |
|
Hom kab mob |
Los ntawm hauv qab |
Los ntawm hauv qab los yog saum toj |
|
Kev Kho Mob Hom |
Los ntawm pem hauv ntej |
Los ntawm pem hauv ntej thiab nram qab |
|
Txee Khoom |
SGCC galvanized ntawv nrog muaj zog corrosion kuj |
SPCC zoo siab txias dov steel phaj |
|
Txee xim |
Lub teeb grey: RAL 7035 |
Lub teeb grey: RAL9007 |
|
Grounding Bar |
7 × M6, 1 × M8 |
||
EMC |
EN300386 Chav Kawm A |
||
Qib tiv thaiv |
IP55 |
IP20 |
|
Roj teeb |
Sab hauv khib & Chaw |
3U, 19-nti khib (raws li qhov tseeb configuration) |
|
Hom roj teeb |
Max. 10pcs DFPA48100-S / DFPA48165-S |
||
Txias hom |
DC Cua Txias |
DC48V 1000W |
TSIS MUAJ |
Power chav faib tsev |
AC Input |
220/384Vac peb-theem plaub-xaim, tau tshaj ib-theem peb-theem: 200-240 Vac / 346-415 Vac ib-theem: 200-240Vac, kev txhawb nqa rau diesel generator inputs |
|
ATS Hom |
ATS-63A1 / ATS-63A2 / ATS-125C1 (yeem, tsuas yog rau ob lub AC inputs) |
||
PV Input |
Input Voltage: 102V (ntau 70-150V), Input Capacity 63A / 2P * 4 |
||
DC tso zis |
Voltage: Ib txwm Hom: 42VDC-58VDC, Boost Module: 53.5VDC los txhawb 57VDC tas li (yuav tsum tau nruab nrog Smart Lithium Battery) |
||
Tam sim no Max.36kW (600A) |
|||
Roj teeb ceg |
MCB: 125A × 10 |
||
LLVD Branch |
2 × 125 AMCB, 3 × 63 AMCB (LLVD1) |
||
BLVD Branch |
2 × 32 AMCB, 2 × 40 AMCB, 4 × 63 AMCB, 4 × 63 AMCB, 2 × 125 AMCB |
||
SP D |
AC tswv yim: 40kA (8/20μs) |
||
DC tso zis: 20 kA / max = 40KA, 8/20 μ |
|||
Rectifier |
Input/Output |
Tawm tswv yim 85-300VAC; Tso zis 42-58VDC; Fais fab 3000W, siab tshaj 12 configurations |
|
PV Module |
Input/Output |
Input voltage: DC70-150V Cov zis: 3000W (0-62.5A @-42Vdcto-58Vdc): efficiency ≥ 0.96 (yeem) |
|
Saib xyuas |
Interface Configuration |
DI input: DI * 6, DO tso zis: DO * 6, Kev sib txuas lus interface: RS485 * 1, LAN * 1 |
|
Ib puag ncig-ment |
Ua haujlwm kub |
0ºC txog +45ºC + hnub ci hluav taws xob (txhawb -20ºC yog tias teeb tsa lub thawv ua ntej cua sov)) |
|
Cia Kub |
-40 ℃ ~ + 70 ℃ |
-20 ℃ ~ + 60 ℃ |
|
Ua haujlwm txheeb ze humidity |
5% mus rau 95% (tsis muaj condensing) |
||
Qhov siab |